![Fuji Electric FRENIC-MEGA Скачать руководство пользователя страница 291](http://html1.mh-extra.com/html/fuji-electric/frenic-mega/frenic-mega_instruction-manual_2341853291.webp)
5-172
Ch
ap
. 5
FUNCTION C
O
DES
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
(13) Timer with reset input
Output
Input 1
Input 2
ON timer
Reset
Timer
Output
Timer period
ON
OFF
OFF
OFF
ON
Input 1
Input 2
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
General-purpose timer (U04, etc.)
The table below lists the general-purpose timers available.
Data Function
Description
0
No timer
1
On-delay timer
Turning an input signal ON starts the on-delay timer. When the period specified
by the timer has elapsed, an output signal turns ON.
Turning the input signal OFF turns the output signal OFF.
2
Off-delay timer
Turning an input signal ON turns an output signal ON.
Turning the input signal OFF starts the off-delay timer. When the period specified
by the timer has elapsed, the output signal turns OFF.
3
One-shot pulse output Turning an input signal ON issues a one-shot pulse whose length is specified by
the timer.
4
Retriggerable timer
Turning an input signal ON issues a one-shot pulse whose length is specified by
the timer.
If an input signal is turned ON again during the preceding one-shot pulse length,
however, the logic circuit issues another one-shot pulse.
5
Pulse train output
If an input signal turns ON, the logic circuit issues ON and OFF pulses (whose
lengths are specified by the timer) alternately and repeatedly. This function is used
to flash a luminescent device.
The operation schemes for individual timers are shown below.
(1) On-delay timer
(2) Off-delay timer
OFF
ON
Timer
Input
Output
Timer period
OFF
ON
OFF
ON
OFF
OFF
OFF
ON
Timer
Input
Output
Timer period
OFF
ON
OFF
OFF
ON
ON
ON
OFF
(3) One-shot pulse output
(4) Retriggerable timer
OFF
ON
Timer
Input
Output
Timer period
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
Timer
Input
Output
Timer period
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
ON
10.00秒
Timer period
Less than
timer period
Содержание FRENIC-MEGA
Страница 36: ...2 6 Unit inch mm Refer to Section 2 3 3 9...
Страница 208: ...5 89 Examples of Sequence Circuits 1 Standard sequence 2 Sequence with an emergency switching function...
Страница 356: ...MEMO...
Страница 358: ...Fuji Electric Co Ltd Fuji Electric Corp of America http www fujielectric com fecoa 2011 04 D11 D10...