4-3
The LD/MD-mode inverter is subject to restrictions on the function code data setting range and internal processing as listed below.
Function
codes
Name
LD mode
MD mode
HD mode
Remarks
F21*
DC braking
(Braking level)
Setting range: 0 to 80%
Setting range:
0 to 100%
In the LD/MD mode, a value out
of the range, if specified,
automatically changes to the
maximum value allowable in the
LD mode.
F26
Motor sound
(Carrier frequency)
Setting range:
0.75 to 16 kHz
(0.5 to 30 HP)
0.75 to 10 kHz
(40 to 100 HP)
0.75 to 6 kHz
(125 to 900 HP)
0.75 to 4 kHz
(1000 HP)
Setting range:
0.75 to 2 kHz
(150 to 800 HP)
Setting range:
0.75 to 16 kHz
(0.5 to 100 HP)
0.75 to 10 kHz
(125 to 800 HP)
0.75 to 6 kHz
(900 and 1000 HP)
F44
Current limiter
(Level)
Initial value: 130% Initial value: 145% Initial value: 160%
Switching the drive mode
between LD, MD and HD with
function code F80 automatically
initializes the F44 data to the
value specified at left.
F03*
Maximum
frequency
Setting range: 25 to 500 Hz
Upper limit: 120 Hz
Setting range:
25 to 500 Hz
Upper limit:
500 Hz
In the LD/MD mode, if the
maximum frequency exceeds
120 Hz, the actual output
frequency is internally limited to
120 Hz.
―
Current indication
and output
Based on the rated
current level for
LD mode
Based on the rated
current level for
MD mode
Based on the rated
current level for
HD mode
―
Even switching to the MD/HD mode cannot automatically change the motor rated capacity (P02*), so configure the P02* data to
match the applied motor rating as required.
Note: For 7.5 HP and smaller, when LD mode is selected, the HD mode specification applies.
4.1.5 Selecting a desired motor drive control
The FRENIC-MEGA supports the following motor drive control.
F42*
data
Drive control
Basic
control
Speed
feedback
Drive control
class
Speed control
Other restrictions
0
V/f control
with slip compensation inactive
V/f
control
Disable V/f
Frequency control
―
1
Dynamic torque vector control
Frequency control
with slip compensation
―
2
V/f control
with slip compensation active
―
3
V/f control
with speed sensor
Enable PG
V/f
Frequency control
with automatic speed
regulator (ASR)
Maximum
frequency: 200 Hz
4
Dynamic torque vector control
with speed sensor
5
Vector control
without speed sensor
Vector
control
Estimated
speed
w/o PG
Speed control
with automatic speed
regulator (ASR)
Maximum
frequency: 120 Hz
Not available for
MD-mode
inverters.
6
Vector control
with speed sensor
Enable w/
PG
Maximum
frequency: 200 Hz
V/f control with slip compensation inactive
Under this control, the inverter controls a motor with the voltage and frequency according to the V/f pattern specified by function
codes. This control disables all automatically controlled features such as the slip compensation, so no unpredictable output
fluctuation results, enabling stable operation with constant output frequency.