5-87
Circuit Diagram and Configuration
Main Circuit
Configuration of Control Circuit
Summary of Operation
Input
Output
(Status signal and magnetic contactor)
Inverter
operation
ISW50
or
ISW60
Run
command
SW52-1
52-1
SW52-2
52-2
SW88
88
OFF
(Commercial power)
ON
OFF OFF
ON
OFF
OFF OFF
ON
(Inverter)
ON
ON
ON OFF
ON
OFF OFF
Timing Scheme
Switching from inverter operation to commercial-power operation
ISW50
/
ISW60
: ON
→
OFF
(1) The inverter output is shut OFF immediately (Power gate IGBT OFF)
(2) The inverter primary circuit
SW52-1
and the inverter secondary side
SW52-2
are turned OFF immediately.
(3) If a run command is present after an elapse of t1 (0.2 sec + time specified by H13), the commercial power circuit
SW88
is turned ON.