5-116
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
Ch
ap
. 5
FUNCTION C
O
DES
5.2.5
H codes (High Performance Functions)
H03 Data
Initialization
H03 initializes the current function code data to the factory defaults or initializes the motor parameters.
To change the H03 data, it is necessary to press the
+
keys or
+
keys (simultaneous keying).
Data for H03
Function
0
Disable initialization (Settings manually made by the user will be retained.)
1
Initialize all function code data to the factory defaults
2
Initialize motor 1 parameters in accordance with P02 (Rated capacity) and P99 (Motor 1 selection)
3
Initialize motor 2 parameters in accordance with A16 (Rated capacity) and A39 (Motor 2 selection)
4
Initialize motor 3 parameters in accordance with b16 (Rated capacity) and b39 (Motor 3 selection)
5
Initialize motor 4 parameters in accordance with r16 (Rated capacity) and r39 (Motor 4 selection)
• To initialize the motor parameters, set the related function codes as follows.
Step Item
Action
Function code
1st motor
2nd motor
3rd motor
4th motor
(1)
Motor selection
Selects the motor type
P99
A39
b39
r39
(2)
Motor
(rated capacity)
Sets the motor capacity
(HP)
P02 A16 b16 r16
(3)
Data
initialization
Initialize motor
parameters
H03 = 2
H03 = 3
H03 = 4
H03 = 5
Function code data to
be initialized
If "Data = 0, 1, 3, or 4"
in Step (1)
P01, P03,
P06 to P23,
P53 to P56,
H46
A15, A17,
A20 to A37,
A53 to A56
b15, b17,
b20 to b37,
b53 to b56
r15, r17,
r20 to r37,
r53 to r56
If "Data = 2" in Step
(1), function codes
listed at the right are
also initialized
F04, F05
A02, A03
b02, b03
r02, r03
• Upon completion of the initialization, the H03 data reverts to "0" (factory default).
• If P02, A16, b16 or r16 data is set to a value other than the nominal applied motor rating, data initialization with H03
internally converts the specified value forcibly to the standard nominal applied motor rating. (Refer to Table B in Section
5.1 "Function Code Tables.")
• Motor parameters to be initialized are for motors listed below under V/f control. When the base frequency, rated voltage,
and the number of poles are different from those of the listed motors, or when non-standard motors are used, change the
rated current data to that printed on the motor nameplate.
Motor selection
V/f control data
Data = 1
HP rating motors
4 poles
230 V/60 Hz, 460 V/60 Hz
Data = 2
Fuji motors exclusively designed for
vector control
4 poles
―
/50 Hz,
―
/50 Hz
Data = 0 or 4
Fuji standard motors, 8-series
4 poles
200 V/50 Hz, 400 V/50 Hz
Data = 3
Fuji standard motors, 6-series
4 poles
200 V/50 Hz, 400 V/50 Hz
When accessing function code P02 with the keypad, take into account that P02 data automatically updates data of
function codes P03, P06 through P23, P53 through P56, and H46. Also, when accessing function code A16, b16 or
r16, data of related function codes for each are automatically updated.