![Fuji Electric FRENIC-MEGA Скачать руководство пользователя страница 227](http://html1.mh-extra.com/html/fuji-electric/frenic-mega/frenic-mega_instruction-manual_2341853227.webp)
5-108
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
Ch
ap
. 5
FUNCTION C
O
DES
Multi-frequency 1 to 15 (C05 through C19)
Data setting range: 0.00 to 500.00 (Hz)
The combination of
SS1
,
SS2
,
SS4
and
SS8
and the selected frequencies are as follows.
SS8 SS4 SS2 SS1
Selected frequency command
OFF
OFF
OFF
OFF
Other than multi-frequency *
OFF OFF OFF ON
C05 (multi-frequency 1)
OFF OFF ON
OFF
C06 (multi-frequency 2)
OFF OFF ON
ON
C07 (multi-frequency 3)
OFF
ON
OFF
OFF
C08 (multi-frequency 4)
OFF
ON OFF ON
C09 (multi-frequency 5)
OFF
ON
ON
OFF
C10 (multi-frequency 6)
OFF
ON
ON
ON
C11 (multi-frequency 7)
ON
OFF
OFF
OFF
C12 (multi-frequency 8)
ON OFF OFF ON
C13 (multi-frequency 9)
ON OFF ON
OFF
C14 (multi-frequency 10)
ON OFF ON
ON
C15 (multi-frequency 11)
ON
ON
OFF
OFF
C16 (multi-frequency 12)
ON
ON OFF ON
C17 (multi-frequency 13)
ON
ON
ON
OFF
C18 (multi-frequency 14)
ON
ON
ON
ON
C19 (multi-frequency 15)
* "Other than multi-frequency" includes frequency command 1 (F01), frequency command 2 (C30) and other command
sources except multi-frequency commands.
When enabling PID control (J01 = 1, 2, or 3)
Under the PID control, a multi-frequency command can be specified as a preset value (3 different frequencies). It can also be
used for a manual speed command even with the PID control being canceled (
Hz
/
PID
= ON) or for a primary reference
frequency under the PID dancer control.
• PID command
SS8 SS4
SS1,
SS2
Command
OFF
OFF
–
Command specified by J02
OFF
ON –
Multi-frequency
by
C08
ON OFF –
Multi-frequency
by
C12
ON
ON –
Multi-frequency
by
C16
C08, C12, and C16 can be specified in increments of 1 Hz. The following gives the conversion formula between the PID
command value and the data to be specified.
Data to be specified = PID command (%)
×
Maximum frequency (F03)
÷
100
PID command (%)
=
Data to be specified (C08, C12, C16)
×
100
Maximum frequency (F03)
• Manual speed command
SS8, SS4
SS2
SS1
Selected frequency command
–
OFF
OFF
Other than multi-frequency
– OFF ON
C05 (Multi-frequency 1)
–
ON
OFF
C06 (Multi-frequency 2)
–
ON
ON
C07 (Multi-frequency 3)