FR500A&FR510A Series Vector Control Inverter
- 44 -
5.1 Five LED (digital) display indicators
Fig.5-1 LED indicators
5.2 Standard Function Parameters
Table 5-1 Standard Function Parameters
Param.
Parameter Name
Setting Range
Default
Attr
Group F00: System Parameters
F00.00
Setting of User Password
0
~
65535
0
×
F00.01
Display of Parameters
0: Display all parameters
0
×
1: Only display F00.00, F00.01 and
user-defined parameters
F17.00
~
F17.29
2: Only display A0-00, A0-01, and the
parameters different with factory
default
F00.02
Parameter Protection
0: All parameter programmable
0
×
1: Only F00.02 and this parameter
programmable
F00.03
G/P type display
0: G type (constant torque load)
0
×
1: P type (variable torque load
e.g. fan and pump)
F00.04
Parameter Initialization
0: No operation
0
×
1: Restore all parameters to factory
default
(excluding motor parameters)
2: Clear fault record
3: Back up current user parameters
4: Restore user backup parameters
5: Restore factory default.
(include motor parameter)
6: Power consumption zero clearing
(U00.35)
F00.06
Parameter editing mode
0:Editable via keypad and RS485.
0
×
1:Editable via keypad
2:Editable via RS485
F00.07
Motor selection
0: Motor 1
1: Motor 2
0
×
F00.08
Motor 1 control mode
Unit’s place: Motor 1 control mode
0: V/F control
1:Sensor-less vector control 1
2: Sensor-less vector control 2
3: Vector control with PG card
1
×
Ten’s place: Motor 2 control mode