FR500A&FR510A Series Vector Control Inverter
- 45 -
0: V/F control
1:Sensor-less vector control 1
2: Sensor-less vector control 2
3. Vector control with PG card
F00.09
DI7/HI input mode
0: Digital input terminal 7
0
×
1: Pulse input
F00.10
AI1\AI2\AI3 input mode
Unit's place: AI1
0: Analog input
1: Digital input
000
×
Ten’s place: AI2
(same as AI1)
Hundred’s place: AI3
(same as AI1)
F00.11
Y2/HO input mode
0: Digital 0utput terminal 2
0
×
1: Pulse output
F00.12
PWM optimization
Unit's place: PWM modulation mode
0: Fixed carrier
1: Random carrier
2: Derating of fixed carrier
3: Derating of random carrier
500
×
Ten’s place: PWM modulation mode
0: Seven-segment mode
1: Five-segment mode
2: Five-segment and
seven-segment automatic
switchover
Hundred’s place: over-modulation
coefficient
0: Invalid
1~9: 1.01~1.09 times of
over-modulation
F00.13
Carrier frequency
0.700
~
16.000kHz
Model
defined
△
F00.14
Upper carrier frequency
0.700
~
16.000kHz
8.000kHz
×
F00.15
Lower carrier frequency
0.700
~
16.000kHz
2.000kHz
×
F00.16
Output voltage
5.0
~
150.0%
100.0%
×
F00.17
AVR
0: Disabled
1
×
1: Enabled
2: AVR is disabled if the DC
bus voltage > the rated
voltage of DC bus, and it will be
enabled if the DC bus voltage≤the
rated voltage of DC bus.
F00.18
Fan control
0: Run at power-on
1
×
1: Fan working during running
F00.19
Factory password
0
~
65535
0
×
F00.20
Inverter rated power
0.2
~
1000.0kW
Model
defined
⊙
F00.21
Inverter rated voltage
60
~
660V
Model
defined
⊙
F00.22
Inverter rated current
0.1
~
1500.0A
Model
defined
⊙
F00.23
Software version
0.00
~
655.35
Model
defined
⊙
F00.24
Dealer password
0
~
65535
0
×
F00.25
Run time setting
0
~
65535h(0: Invalid)
0h
×