FR500A&FR510A Series Vector Control Inverter
- 79 -
Chapter 6 Specification of Parameters
Group F00 System Parameters
F00.00
Setting of user password
Range: 0
~
65535
Default: 0
Setting of password:
A number greater than 100 could be set as a user password by entering this password into F00.00
and pressing ENT key to confirm once, the password setting will take effect as long as there is
no operation on keypad within 2 minutes, or cutting the power off and power up again . After a
password has been set and taken effect, you must enter the correct password in order to enter the
menu. If the entered password is incorrect you cannot view or modify parameters.
Change password:
Access F00.00 after entering the original password (at this point, F00.00 displays setting of user
password) and set the new password following the above-noted procedure.
Password clearance:
Access F00.00 after entering the original password (at this point, F00.00 displays setting of user
password); F00.00 is set to 0 and press ENT key to make confirmation. In this way, password is
successfully cleared and the password protection function is disabled.
F00.01
Display of parameters
Range: 0
~
2
Default: 0
0: Display all parameters
1: Only display F00.00, F00.01 and user-defined parameters
2: Only display F00.00, F00.01 and the parameters different with factory default
F00.02
Parameter protection
Range: 0
~
1
Default: 0
0: All parameter programming allowed
1: Only this parameter programming allowed
F00.03
G/P type display
Range: 0
~
1
Default: 0
0: G type (constant torque load)
1: P type (variable torque load e.g. fan and pump)
F00.04
Parameter initialization
Range:0
~
6
Default: 0
0: No operation
1: Restore all parameters to factory default (excluding motor parameters)
If F00.04 is set to 1, most function codes are restored to the default settings except motor
parameters, fault records, accumulative running time, and accumulative power-on time.
2: Clear fault record
If F00.04 is set to 2, all fault record of Group U01 will be cleared.
3: Back up current user parameters
If F00.04 is set to 3, the current parameter settings are backed up, helping you to restore the
setting if incorrect parameter setting is performed.
4: Restore all parameters to backup parameters
If F00.04 is set to 4, the previous backup user parameters are restored.
5: Restore factory default (include motor parameters)
The same as function 1, but this include motor parameters
6: Power consumption zero clearing
After setting F00.04 as 6, U00.35 parameter cleared to zero
F00.06
Parameter editing mode
Range:0
~
2
Default: 0
0: Editable via keypad and RS485
1: Editable via keypad
2: Editable via RS485
F00.07
Motor selection
Range
:
0
~
1
Default:0
0
:
Motor 1
The first set of motors and motor control parameters are adopted.
1
:
Motor 2
Using the second set of motors and motor control parameters