FR500A&FR510A Series Vector Control Inverter
- 50 -
output encoder
(FR510A only)
F04.10
Filtering time of digital
input terminal
0.000
~
1.000s
0.010s
△
F04.11
Delay time before
terminal
DI1 is valid
0.0
~
300.0s
0.0s
△
F04.12
Delay time before
terminal
DI2 is valid
0.0
~
300.0s
0.0s
△
F04.13
Terminal DI1
~
DI5
positive/negative logic
DI5, DI4, DI3, DI2, DI1
00000
×
0: Positive logic(Terminals are on at
0V/off at 24V)
1: Negative Logic (Terminals are off
at 0V/on at 24V)
F04.14
Terminal DI6
~
AI3
positive/negative logic
AI3, AI2, AI1, DI7, DI6
00000
×
0: Positive logic
1: Negative Logic
F04.15
FWD/REV terminal
control mode
0: Two-wire mode 1
0
×
1: Two-wire mode 2
2: Three-wire mode 1
3: Three-wire mode 2
F04.16
Terminal UP/DOWN
frequency adjustment
control
Unit's place: action when stop
0: Clear
1: Holding
00001
×
Ten’s place: action on power loss
0: Clear
1: Holding
Hundreds place: integral function
0: No integral function
1: Integral function enabled
Thousand’s place: Select if it can be
reduced to negative frequency
0: Disable
1: Enable
Ten thousand’s place: Jog action to
clear UP/DOWN
0: Not Clear
1: Clear
F04.17
Terminal UP/DOWN
frequency change step
size
0.00
~
50.00Hz 0.00:Disabled
1.00Hz/
200ms
△
F04.18
Terminal action selection
when power on
0: Level effective
0
×
1: Edge tLevel
effective(When power on)
2: Edge tLevel
effective(Every start)
F04.19
Delay time before
terminal
DI1 is invalid
0.0
~
300.0s
0.0s
△
F04.20
Delay time before
terminal
DI2 is invalid
0.0
~
300.0s
0.0s
△
Group F05 Digital Output