![Frecon FR500-4T-0.7G/1.5PB Скачать руководство пользователя страница 55](http://html1.mh-extra.com/html/frecon/fr500-4t-0-7g-1-5pb/fr500-4t-0-7g-1-5pb_user-manual_2329263055.webp)
FR500A&FR510A Series Vector Control Inverter
- 55 -
async motor 1
defined
F08.13
Field weakening coeff 1
of async motor 1
0.0
~
100.0
87%
×
F08.14
Field weakening coeff 2
of async motor 1
0.0
~
100.0
75%
×
F08.15
Field weakening coeff 3
of async motor 1
0.0
~
100.0
70%
×
F08.16
PMSM stator resistance
(FR510A only)
0.001
~
65.535Ω
Model
defined
×
F08.17
PMSM d-axis inductance
(FR510A only)
0.01
~
655.35mH
Model
defined
×
F08.18
PMSM d-axis inductance
(FR510A only)
0.01
~
655.35mH
Model
defined
×
F08.19
PMSM back EMF
(FR510A only)
0
~
65535V
Model
defined
×
F08.20
Installation angle of
encoder (FR510A only)
0.0
~
359.9°
0.0°
×
F08.21
Pole number of motor
0
~
1000
4
×
F08.22
Find encoder origin at
beginning (FR510A only)
0: Not find
1: Find
1
×
F08.23
Encoder line number
(FR510A only)
0
~
10000
1024
×
F08.24
Encoder type
(FR510A only)
0: ABZ encoder
1: UVW encoder
2: Rotary encoder
3: ECN1313
4: Sine-cosine encoder
0
×
F08.25
AB Phase Sequence of
ABZ Incremental
Encoder (FR510A only)
0: Positive
1: Negative
0
×
F08.26
Speed feedback PG
disconnection detection
time (FR510A only)
0.0
:
Invalid
0.1
~
10.0s
0.0s
×
F08.27
Speed Ratio of Motor to
Encoder (FR510A only)
0.001
~
60.000
1.000
×
F08.28
Pole pairs of rotary
encoder
(FR510A only)
1
~
100
1
×
F08.30
Autotuning of motor 1
0: No autotuning
0
×
1: Static autotuning of motor
2: Rotary autotuning of motor
Group F09 V/f Control Parameters of Motor 1
F09.00
V/f curve setting
00: Linear V/F
0
×
01: Multi-stage V/F
02: 1.2nd power V/F
03: 1.4nd power V/F
04: 1.6nd power V/F
05: 1.8nd power V/F
06: 2.0nd power V/F
07: V/F complete separation
08: V/F half separation
09: 1.2 power inverse curve V/F
10: 1.4 power inverse curve V/F
11: 1.6 power inverse curve V/F
12: 1.8 power inverse curve V/F
13: 2.0 power inverse curve V/F
F09.01
Torque boost
0.1%–30.0% 0.0% (fixed torque
0.0%
△