FR500A&FR510A Series Vector Control Inverter
- 56 -
boost)
F09.02
Cut-off frequency of
torque boost
0.00
~
Fmax
50.00Hz
△
F09.03
Multi-point V/F frequency
1(F1)
0.00
~
F09.05
0.00Hz
△
F09.04
Multi-point V/F voltage 1
(V1)
0.0
~
100.0
5.0%
△
F09.05
Multi-point V/F frequency
2(F2)
F09.03
~
F09.05
5.00Hz
△
F09.06
Multi-point V/F voltage 2
(V2)
0.0
~
100.0
14.0%
△
F09.07
Multi-point V/F frequency
3(F3)
F09.05
~
F09.09
25.00Hz
△
F09.08
Multi-point V/F voltage 3
(V3)
0.0
~
100.0
50.0%
△
F09.09
Multi-point V/F frequency
4(F4)
F09.07
~
rated motor frequency
50.00Hz
△
F09.10
Multi-point V/F voltage 4
(V4)
0.0
~
100.0
Ue=100.0%
100.0%
△
F09.11
V/F slip compensation
gain
0.0
~
300.0%
80.0%
△
F09.12
Stator voltagedrop
compensation gain
0.0
~
200.0%
100.0%
△
F09.13
Excitation boost gain
0.0
~
200.0%
100.0%
△
F09.14
Oscillation Suppression
0.0
~
300.0%
100.0%
△
F09.15
Voltage source for V/F
separation
0: Digital setting (F09.16)
0
×
1: keypad potentiometer
2: AI1
3: Multi-reference
4: Pulse setting ( DI7/HI )
5: PID
6: AI2
7: AI3
F09.16
Voltage digital setting for
V/F separation
0 V to rated motor voltage
0.0%
△
F09.17
Voltage rise time of V/F
separation
0.0
~
6000.0s
It indicates the time for the
voltage rising from 0 V to rated
Motor voltage.
0.1s
△
F09.18
Set the IQ filter time
below 0.5Hz in VVF
mode
F09.19
~
3000ms
500ms
×
F09.19
Set the IQ filter time
above 2Hz in VVF mode
1ms
~
F09.18
100ms
×
F09.20
Torque revision when run
forward
0.0
~
5.0%
0.0%
△
F09.21
Torque revision when run
reverse
0.0
~
5.0%
1.0%
△
F09.22
PMSM acceleration
current compensation
setting
(FR510A only)
0.0
~
200.0%
0.0%
△
F09.23
PMSM compensation
time decreased after
acceleration
(FR510A only)
0.0
~
100.0s
2.0s
△
F09.24
PMSM ID current value
0.0
~
200.0%
0.0%
△