FR500A&FR510A Series Vector Control Inverter
- 100 -
1: Edge t Electrical level effective(When power on)
When terminal is given running command, the terminal is detected to jump from OFF to ON and
maintain ON, inverter start to run.
2: Edge t Electrical level effective(Every start)
When terminal is given running command, the terminal is detected to jump from OFF to ON and
maintain ON, inverter start to run.
Group F05 Digital Output
F05.00
Y1 output function
Range:0
~
99
Default:1
F05.01
Y2/HO output function
(when used as Y2)
Range:0
~
99
Default:3
F05.02
Relay 1 output function
Range:0
~
99
Default:2
F05.03
Relay 2 output function
Range:0
~
99
Default:11
Define the functions of digital output terminals Y1 & Y2, relay 1 and relay 2.Output terminal
function selections are as follows:
Settin
g
Corresponding
function
Description
0
No output
Output terminal is disabled, and there is no output.
1
Drive is running
The output is ON when the drive is running, and output is
OFF when drive stopped.
2
Fault output
When the drive is in fault, outputs ON.
3
Frequency-level
detection FDT1 output
Refer to the descriptions of F05.10 and F05.11.
4
Frequency-level
detection FDT2 output
Refer to the descriptions of F05.12 and F05.13.
5
Drive in 0Hz running
1(no output at stop)
When be running at 0Hz, this corresponding terminal
outputs ON signal. No ON signal will be output at stop.
6
Drive in 0Hz running
2(output at stop)
Outputs ON signal when is running at 0Hz and also outputs
ON signal at stop.
7
Upper limit frequency
attained
When output frequency attains F01.09 (upper limit
frequency), outputs ON.
8
Lower limit frequency
attained (no output at
stop)
When output frequency attains F01.10 (lower limit
frequency), outputs ON. In the stop state, the terminal
becomes OFF.
9
Frequency attained
Refer to the descriptions of F05.09.
10
Ready for RUN
If the AC drive main circuit and control circuit become
stable, and the AC drive detects no fault and is ready for
RUN, the terminal becomes ON.
11
Drive (motor)
overloaded alarm
In case drive output current exceeds F11.19 (overload
alarm threshold) and its last time exceeds F11.20 (overload
alarm activated time that exceeding threshold), outputs ON.
Refer to parameters F11.18
~
F11.20 for information with
regard to drive (motor) overloaded alarm.
12
Drive overheat alarm
When drive internally detected temperature exceeds F11.21
(Drive overheat alarm threshold), ON signal will be output.
13
Current running time
attained
When current running time attains the value of F05.14,
corresponding terminal outputs ON. Current running time is
cleared when stop.
14
Accumulative
power-on time
attained
When accumulative power-on time attains the value of
F05.15, corresponding terminal outputs ON. Accumulative
power-on time is maintained when stop.
15
Accumulative running
time attained
When accumulative running time attains the value of
F05.16, corresponding terminal outputs ON. Accumulative
running time is maintained when stop.
16
PLC cycle completed
Upon the completion of a cycle of simple PLC running, ON
signal with a width of 250ms will be output.