FR500A&FR510A Series Vector Control Inverter
- 26 -
FR500A-4T-037GB
160
100
16
16
M6
FR500A-4T-037G/045P(B)
200
125
25
16
M8
FR500A-4T-045G/055P(B)
200
125
35
25
M8
FR500A-4T-055G/075P(B)
250
160
50
25
M10
FR500A-4T-075G/090P(B)
250
160
70
35
M10
FR500A-4T-090G/110P(B)
350
350
120
60
M10
FR500A-4T-110G/132P
400
400
150
75
M12
FR500A-4T-132G/160P
500
400
185
95
M12
FR500A -4T-185G/200P
600
600
185
95
M10
FR500A -4T-200G/220P
600
600
150*2
150
M10
FR500A -4T-220G/250P
600
600
150*2
150
M12
FR500A -4T-250G/280P
800
600
185*2
95*2
M12
FR500A -4T-280G/315P
800
800
185*2
95*2
M12
FR500A -4T-315G/355P
800
800
150*3
75*3
M16
FR500A -4T-355G/400P
800
800
150*4
75*4
M16
FR500A -4T-400G/450P
1000
1000
150*4
75*4
M16
FR500A -4T-450G
1200
1200
180*4
90*4
M16
*Note
:
The model of FR510A series inverter only needs to replace FR500A in the above
table with FR510A
3.6.2 Reactor
In order to prevent high grid power to the input power circuit of inverter and damage the
rectifier components, need to install AC reactor in input side of inverter, and it can also improve the
input power factor
When the motor cable is over 50 meters, because of the higher leakage current due to the
capacitance effect of long cable to the grounding, inverter will occur over current protection frequently,
meanwhile to avoid motor insulation damage, need to install output reactor for the compensation.
DC reactor can improve power factor, avoid rectifier damage caused by higher input current, and
avoid the rectifier circuit damage by the harmonic due to the grid power surge or phase controlled
load.
Fig 3-4 Reactor
Inverter Power
Input Reactor
DC Reactor
Output Reactor
4.0kw
ACL-4T-4.0
/
OCL-4T-4.0
5.5kw
ACL-4T-5.5
/
OCL-4T-5.5
7.5kw
ACL-4T-7.5
/
OCL-4T-7.5
11kw
ACL-4T-011
/
OCL-4T-011
15kw
ACL-4T-015
/
OCL-4T-015
18.5kw
ACL-4T-018
/
OCL-4T-018
22kw
ACL-4T-022
/
OCL-4T-022
30kw
ACL-4T-030
/
OCL-4T-030
37kw
ACL-4T-037
/
OCL-4T-037
45kw
ACL-4T-045
/
OCL-4T-045
55kw
ACL-4T-055
/
OCL-4T-055
75kw
ACL-4T-075
/
OCL-4T-075
90kw
ACL-4T-090
/
OCL-4T-090
110kw
ACL-4T-110
External optional
OCL-4T-110
132kw
ACL-4T-132
External optional
OCL-4T-132