FR500A&FR510A Series Vector Control Inverter
- 156 -
4.3 Allocation of Register Addresses
name
Description
Function Code
(F00.00
~
U01.99)
High byte function code group number, F00
~
F31, U00, U01,
respectively, corresponding to the high byte address is 00H
~
1FH, 30H,
31H.
Low byte of the group function code number, from 0 to 99 corresponding
to the low byte address is 00H
~
63H.
For example: Modify F01.02 function code value, no power-down when
storing the corresponding register address (referred to as RAM address)
to 0102H.
EEPROM is frequently modified, will reduce the life of the EEPROM. If
you modify the value of the function code-down storage needs, you can
make this function code is the highest position a high address. Note that
this address is only to write, not read.
For example: Modify F01.02 function code value, and the corresponding
need to power down when storing the register address (referred to as
EEPROM address) to 8102H.
Function code group
RAM address high byte
EEPROM address high byte
F00
0x00
0x80
F01
0x01
0x81
F02
0x02
0x82
F03
0x03
0x83
F04
0x04
0x84
F05
0x05
0x85
F06
0x06
0x86
F07
0x07
0x87
F08
0x08
0x88
F09
0x09
0x89
F10
0x0A
0x8A
F11
0x0B
0x8B
F12
0x0C
0x8C
F13
0x0D
0x8D
F14
0x0E
0x8E
F15
0x0F
0x8F
F16
0x10
0x90
F17
0x11
0x91
F18
0x12
0x92
F19
0x13
0x93
F20
0x14
0x94
F21
0x15
0x95
F22
0x16
0x96
U00 (Read Only)
0x30
--
U01 (Read Only)
0x31
--
4.4 Address and control command functions: (write only)
Command word address
Command Function
2000H
0001: Forward run
0002: Reverse Run
0003: Inching Forward
0004: Reverse Jog
0005: Slowdown stop
0006: Freewheel
0007: Fault reset
2001H
Communication setting frequency (0
~
Fmax (Unit: 0.01Hz))
2002H
PID given range (0 to 1000, 1000 corresponds to 100.0%)
2003H
PID feedback range (0
~
1000, 1000 corresponds to 100.0%)