FR500A&FR510A Series Vector Control Inverter
- 145 -
Positive and negative logic of VD0 output terminal:
Positive logic: If terminal is invalid, then output 0, if terminal is valid, then output 1.
Negative logic: If terminal is invalid, then output 1, if terminal is valid, then output 0.
Group U00 Status Monitoring
Group U00 is used to monitor the AC drive's running state. You can view the parameter values by
using keypad, convenient for on-site commissioning, or from the host computer by means of
communication (address: 0x3000
~
0x3020). Status monitoring parameters in the running and stop
state are defined by F16.03 and F16.103.
U00.00
Running frequency
Range:0.00
~
Fup
Default:0.00Hz
U00.01
Set frequency
Range:0.00
~
Fmax
Default:0.00Hz
U00.02
Output voltage
Range:0
~
660V
Default:0V
U00.03
Output current
Range:0.0
~
3000.0A
Default:0.0A
U00.04
Output power
Range:-3000.0
~
3000.0kW
Default:0.0kW
U00.05
Estimated Motor Speed
Range:0
~
60000rpm
Default:0rpm
U00.06
Bus voltage
Range:0
~
1200V
Default:0V
U00.07
Synchronous
Frequency
Range:0.00
~
Fup
Default:0.00Hz
U00.08
PLC step
Range:1
~
15
Default:1
U00.09
Program Operation
Time
Range:0.0
~
6000.0s(h)
Default:0.0s(h)
U00.10
PID set
Range:0
~
60000
Default:0
U00.11
PID feedback
Range:0
~
60000
Default:0
They display the PID setting value and PID feedback value.
PID setting = PID setting (percentage)
F13.03
PID feedback = PID feedback (percentage)
F13.03
U00.12
Status of DI1
~
DI5
digital input terminal
Range:00000
~
11111
Default:00000
0 means terminal input status is OFF, while 1 means terminal input status is ON.
Unit's place: DI1
Decade: DI2
Hundreds place: DI3
Thousands place: DI4
U00.13
Status of DI6
~
DI7
digital input terminal
Range: 00
~
11
Default: 00
Ten thousands place: DI5
0 means terminal input status is OFF, while 1 means terminal input status is ON.
Unit's place: DI6
Decade: DI7
U00.14
Status of digital output
terminal
Range: 0000
~
1111
Default: 0000
0 means terminal input status is OFF, while 1 means terminal input status is ON.
Unit's place: Y1
Decade: Y2
Hundreds place: R1
Thousands place: R2
U00.15
AI1 input
Range: 0.0
~
100.0%
Default: 0.0%
U00.16
AI2 input
Range: 0.0
~
100.0%
Default: 0.0%
U00.17
AI3 input
Range: 0.0
~
100.0%
Default: 0.0%
U00.18
Keypad potentiometer
input
Range: 0.0
~
100.0%
Default: 0.0%
U00.19
HI input
Range: 0.00
~
100.00kHz
Default: 0.00kHz
U00.20
AO1 output
Range: 0.0
~
100.0%
Default: 0.0%