FR500A&FR510A Series Vector Control Inverter
- 125 -
PLC automatically starts another cycle after finishing one until there is a stop command, shown
as Fig. 6-24.
Fig. 6-32
Ten’s place: started mode
0: Continue to run from the step of stop (or fault)
At the moment drive stop, the drive automatically records the running time of current step. When
restarted, the drive will gets into this step, continue to run the remanent time with the frequency of this
step.
1: Run from the first step “multi-step reference 0”
When restarted after stop, the drive will start to run from “step 0”.
2: Run from the Eighth step “multi-step reference 8”
When restarted after stop, the drive will start to run from “step 8”.
3: Run from the Fifteenth step “multi-step reference 15”
When restarted after stop, the drive will start to run from “step15”.
Hundreds place: power loss memory
0: Memory disabled on power loss
The drive does not memorize PLC running status on power loss and starts the running from step
0 after power up again.
1: Memory enabled on power loss
The drive saves PLC running status on power loss, including the running step, running frequency
and finished running time at the moment of power loss. After the next power up, the running will be
continued in accordance with the memorized status.
Thousands place: unit of simple PLC running time
0: Second
1: Hour
Set the unit of running time and Accel/Decel time of simple PLC.
F12.18
Running time of step 0
Range:0.0
~
6000.0s(h)
Default:0.0s(h)
F12.19
Running time of step 1
Range:0.0
~
6000.0s(h)
Default:0.0s(h)
F12.20
Running time of step 2
Range:0.0
~
6000.0s(h)
Default:0.0s(h)
F12.21
Running time of step 3
Range:0.0
~
6000.0s(h)
Default:0.0s(h)
F12.22
Running time of step 4
Range:0.0
~
6000.0s(h)
Default:0.0s(h)
F12.23
Running time of step 5
Range:0.0
~
6000.0s(h)
Default:0.0s(h)
F12.24
Running time of step 6
Range:0.0
~
6000.0s(h)
Default:0.0s(h)
F12.25
Running time of step 7
Range:0.0
~
6000.0s(h)
Default:0.0s(h)
F12.26
Running time of step 8
Range:0.0
~
6000.0s(h)
Default:0.0s(h)
F12.27
Running time of step 9
Range:0.0
~
6000.0s(h)
Default:0.0s(h)
F12.28
Running time of step 10
Range:0.0
~
6000.0s(h)
Default:0.0s(h)
F12.29
Running time of step 11
Range:0.0
~
6000.0s(h)
Default:0.0s(h)
F12.30
Running time of step 12
Range:0.0
~
6000.0s(h)
Default:0.0s(h)