- 163 -
Appendix C: PG Card
FR510A series is equipped with PG cards showed as below, as optional parts, is the necessary
part for inverter with closed loop vector control mode. PG card feedback the real-time speed of motor
through the signal acquisition from encoder to achieve the precise control of motor speed and steering
Model
Description
Connection mode
EXC-PG01
The differential input PG card
Terminal connection
EXC-PG02
Open collector,push input PG card
Terminal connection
EXC-PG03
Rotary transformer PGcard
DB9 interface
EXC-PG04
UVW encoder PG card
Terminal connection
EXC-PG05
ECN1313 PG card
Terminal connection
EXC-PG06
Sin-Cos encoder PG card
DB15 interface
Relative Parameters
Function
code
Code Name
Setting Range
Default
Attr
F00.08
Motor control
method
Unit’s place: Motor1 control method
11
×
0: V/F control
1: Sensor-less vector control mode1
2: Sensor-less vector control mode2
3: Close-loop control(with PG card)
Ten’s place: Motor2 control method
0: V/F control
1: Sensor-less vector control mode1
2: Sensor-less vector control mode2
3: Close-loop control(with PG card)
F08.23
Encoder line
count
0-65535
1024
×
F08.24
Encoder
selection
0: ABZ incremental encoder
0
×
1: UVW incremental encoder
2: Rotary transformer
3: ECN1313
4: Sin-Cos encoder
F08.25
AB phase
sequence
0: Positive
0
×
1: Negative
F08.30
Auto-tuning
0: No autotuning
0
×
1: Static autotuning of motor
2: Rotary autotuning of motor
Set these parameter according to different encoder
Function code expaination:
1)F00.08 = 33(Close-loop control,with PG card)
2)When choosing ABZ incremental encoder, F08.24 should be rightly set.
3)When choosing ABZ incremental encoder, need to check that AB phase sequence is the same
with frequency.