![Frecon FR500-4T-0.7G/1.5PB Скачать руководство пользователя страница 109](http://html1.mh-extra.com/html/frecon/fr500-4t-0-7g-1-5pb/fr500-4t-0-7g-1-5pb_user-manual_2329263109.webp)
FR500A&FR510A Series Vector Control Inverter
- 109 -
Define output filtering time of AO1 terminal.
F07.06
AO2 offset
Range:-100.0
~
100.0%
Default:0.0%
F07.07
AO1 gain
Range:-2.000
~
2.000
Default:1.000
F07.08
AO2 filtering time
Range:0.000
~
10.000s
Default:0.000s
Adjustment method of AO2 output curve is the same as AO1.
F07.09
HO maximum output
pulse frequency
Range:0.01
~
100.00kHz
Default:50.00kHz
This parameter sets the maximum output frequency when Y2/HO terminal is selected as
high-speed pulse output.
F07.10
HO output filtering time
Range:0.000
~
10.000s
Default:0.010s
Set the filtering time of HO high-speed pulse output. Filtering can change the change rate of
output pulse frequency. The longer the filtering time is, the lower the change rate of output pulse
frequency would be.
F07.11
Ho output encoder pulse
proportion 1
Range
:
0.00
~
10.00
Default
:
1.00
F07.12
Ho output encoder pulse
proportion 2
Range
:
0.00
~
10.00
Default
:
1.00
When Y2 / Ho outputs ABZ pulse as high-speed pulse output terminal, the ratio of ABZ pulse
output can be set by setting two function codes f07.11 and f07.12. The switching of ratio 1 and 2 is
determined by terminal function 74
。
Group F08 Parameters of Motor 1
0: Three phase asynchronous motors
1: Sync motor(PMSM)
2: Single phase asynchronous motors(remove capacitance)
3: Single phase asynchronous motors(not remove capacitance)
Set the parameters according to the motor nameplate no matter whether V/F control or vector
control is adopted.
To achieve better V/F or vector control performance, motor auto-tuning is required. The motor
auto-tuning accuracy depends on the correct setting of motor nameplate parameters.
F08.08
Stator resistance R1 of
async motor 1
Range:0.001
~
65.535Ω
Default: Model defined
F08.09
Rotor resistance R2 of
async motor 1
Range:0.001
~
65.535Ω
Default: Model defined
F08.10
Leakage inductance L1 of
async motor 1
Range:0.001
~
65.535mH
Default: Model defined
F08.11
Mutual inductance L2 of
asynchronous motor 1
Range:0.1
~
6553.5mH
Default: Model defined
F08.12
No-load current of async
motor 1
Range:0.1
~
1500.0A
Default: Model defined
F08.13
Field weakening coeff 1 of
async motor 1
Range:0.0
~
100.0%
Default:87%
(
1.1
)
F08.14
Field weakening coeff 2
of async motor 1
Range:0.0
~
100.0%
Default:75%
(
1.6
)
F08.15
Field weakening coeff 2
of async motor 1
Range:0.0
~
100.0%
Default:70%
(
3
)
F08.00
Motor 1 type selection
Range: 0
~
3
Default: 0
F08.01
Power rating of motor 1
Range:0.1
~
1000.0kW
Default: Model defined
F08.02
Rated voltage of motor 1
Range:60
~
660V
Default: Model defined
F08.03
Rated current of motor 1
Range:0.1
~
1500.0A
Default: Model defined
F08.04
Rated frequency of motor 1
Range:20.00
~
Fmax
Default: Model defined
F08.05
Rated speed of motor 1
Range:1
~
60000rpm
Default: Model defined