FR500A&FR510A Series Vector Control Inverter
- 33 -
AO2-GND
Analog output
terminal 2
AO1, AO2 on the control board
Impedance requirements≥10kΩ
Switch output
Y1-COM
Open collector
output 1
Voltage range:0
~
24V
Current range:0
~
50mA
Y2/HO-COM
Open collector
output 2 OR
High-speed
pulse output
Besides features of Y1, it can be used
for High-speed pulse output channels.
The maximum output
frequency:100kHz
Relay output
R1A-R1C
Normally open
terminal
Contact driving capacity:
AC250V
,
3A
,
COSØ=0.4.
DC 30V
,
1A
R1B-R1C
Normally
closed terminal
R2A-R2C
Normally open
terminal
R2B-R2C
Normally
closed terminal
485
Communication
485+-485-
485
Communication
Terminals
Rate:
4800/9600/19200/38400/57600/
115200bps
Termination resistor is set by the
toggle switch on the control panel
RS485
GND
485
Communication
shielded
ground
Shield
PE
Shield Ground
Ground terminal for shield
Auxiliary
Interface
External
operation
panel interface
Use standard network cable
Maximum cable distance: 50m
Description of Wiring of Signal Terminals:
1
)
Description Use the analog input terminal
Weak analog voltage signals are easy to suffer external interference, and therefore the shielded
cable must be used and the cable length must be less than 20 m, as shown in following figure. When
the analog input signal to an external power supply
,
AI1 Terminal wiring as shown in Fig 3-12
(
a
)
.When the input analog voltage signal is potentiometer
,
AI1 Terminal wiring as shown in Fig 3-12
(
b
)
AI2/AI3 Similar to AI1.
(
a
)
(b)
Fig.3-16 Analog input terminal wiring diagram
2
)
Instructions of Digital Input/output Terminals
Digital input & output signals cables should be as short as possible, shielded, and their shielded
layers should be properly grounded close to the side of drive. The cables should not exceed 20m.
When active drive is selected, take necessary filtering measures against power crosstalk, for
which dry contact control is recommended.
Control cables shall be kept no less than 20cm away from main circuit and strong current lines
(e.g. power lines, motor lines, relay lines and contactor lines) and should not be arranged in parallel
with strong current lines. In case it is inevitable to intersect strong current line, vertical wiring is