FR500A&FR510A Series Vector Control Inverter
- 60 -
Ten's place: compared object
0: Rated current of motor
1: Rated current of drive
Hundred’s place: Fault reported
0:No fault reported
1:Fault reported
Thousand’s place: whether to
decelerate or not when overload
alarm
0: No deceleration
1: Deceleration
Ten thousand's place: given mode
for overload threshold
0: F11.19 set
1: F11.19*VP
2: F11.19*AI1
3: F11.19*AI2
4: F11.19*AI3
F11.19
Overload alarm threshold
20.0
~
200.0%
130.0%
×
F11.20
Overload alarm
activated time that
exceeding threshold
0.1
~
60.0s
5.0s
×
F11.21
Inverter overheat
warning threshold
50
~
overheat Temperature
Model
defined
×
F11.22
Detection level of load
loss
5.0
~
100.0%
20.0%
×
F11.23
Detection time of load
loss
0.1
~
60.0s
5.0s
×
F11.24
Action selection at
instantaneous power
failure
0: Disabled
0
×
1: Deceleration
2: Bus voltage constant control
F11.25
Decel time at
instantaneous power
failure
0.0
~
6000.0s
5.0s
△
F11.26
Rapid current limit
0: Disabled
0
×
1: Enabled
F11.27
Times of automatic
trip(fault) reset
0
~
20
0
×
F11.28
Interval of automatic
trip(fault) reset
0.1
~
100.0s
1.0s
×
F11.29
DO action during fault
auto reset
0: Not act
0
×
1: Act
F11.30
Instantaneous power
off bus voltage
60.0%
~
Recovery voltage
80.0%
△
F11.31
Instantaneous power off
recovery voltage
Power off voltage
~
100.0%
85.0%
△
F11.32
Instantaneous power off
voltage detection time
0.01
~
10.00s
0.10s
△
F11.33
Instantaneous power off
Kp
0.1
~
100.0%
40.0%
△
F11.34
Instantaneous power off
integration time Ti
0.00
~
10.00s
(
0.00: Integration
invalid
)
0.10s
△
F11.35
Motor temperature
sensor type
0:None
1:PT100
2:PT1000
3:KTY84
0
×