FR500A&FR510A Series Vector Control Inverter
- 132 -
F14.07
Command when the length
attained
Range:00
~
12
Default: 0
Units place: stop when the length reaches
0: not stop
1: stop.
When the actual length detected reaches the length set in f14.05, select whether to stop.
The actual length can be cleared through the terminal of "length reset" input of switching value.
Tens: length calculation method
0: pulse by pulse
The length is calculated by measuring the number of pulse inputs of the terminal (the terminal
function is set to 34), and combining with the number of pulses per meter set in f14.06.
1: By maximum frequency
The linear velocity at the current frequency is estimated by setting the corresponding linear velocity
f14.06 at the maximum frequency.
2: Refer to Ai1 channel
Using the method of estimation, by setting the corresponding line speed f14.06 when Ai1 is 100%,
the line speed under the current Ai1 percentage is estimated.
3: Refer to AI2 channel (same as Ai1)
4: Refer to ai3 channel (same as Ai1)
ATTENTION:
When actual length is detected to attain the set length, digital output terminal "length attained"
outputs ON signal no matter the drive is set to stop or not stop.
Actual length is saved at power loss and can be read in both stop and running.
F14.08
Set count value
Range:1
~
65535
Default:1000
F14.09
Designated count value
Range:1
~
65535
Default:1000
The count value needs to be collected by DI terminal. Allocate the corresponding DI terminal with
function 32 (Counter input) in applications. If the pulse frequency is high, DI7/HI must be used.
When the count value reaches the set count value (F14.08), the DO terminal allocated with
function 17 (Set count value reached) becomes ON. Then the counter stops counting.
When the counting value reaches the designated counting value (F14.09), the DO terminal
allocated with function 17 (Designated count value reached) becomes ON. Then the counter continues
to count until the set count value is reached.
F14.09 should be equal to or smaller than F14.08.
Figure 6-28 Reaching the set count value and designated count value
Figure 6-36
ATTENTION:
Actual count value can be cleared through digital input terminal "count clear".
Actual count value is saved at power loss.
F14.10
Wake up frequency
Range: Dormancy
frequency
~
Fmax
Default: 0.00Hz
F14.11
Wake up delay time
Range: 0.0
~
6000.0s
Default: 0.0s