3.8.2 Control circuit terminals
DI1
+24V
DI2
PLC
DI3
COM
DI4
DI5
COM
DI6
Y1 Y2
+10V
R1A R1B R1C
R2A R2B R2C
AO1
AI1
GND
AI2
485+
AI3
485-
PE
DI7/HI
AO2
GND
Fig.3-17 Control circuit terminals
Table 3-7 Description of control circuit terminals
Type
Terminal
Name
Function Description
Power supply
+10V-GND
Ex10 V
power supply
P10 V power supply to
external unit.
Generally, it provides power supply to
external potentiometer with resistance
range of 1–5 kΩ.
Maximum output current: 10 mA
+24V-COM
Ex24V
power
supply Applying
to Overvoltage
Category II
circuit
P24 V power supply to
external unit.
Generally, it provides power supply to
DI/Do terminals and external sensors.
Maximum output current: 200 mA
PLC
Input terminal
of
external power
supply
Connect to +24 V by default.
When DI1-DI7 need to be driven by
external signal, PLC needs to be
connected to external power supply
and be disconnected from +24 V.
Analog input
AI1-GND
Analog input 1
Input voltage range: DC 0
~
10V/0
~
20mA
,
decided by toggle switches
AI1, AI2 on the control board
Impedance: 250 kΩ (voltage input),
250 Ω (current input)
AI2-GND
Analog input 2
AI3-GND
Analog input 3
Input Voltage Range: DC -10
~
+10V
Input impedance:250kΩ
Switch input
DI1- COM
Switch input
terminals 1
Maximum input frequency:200Hz
Impedance:2.4kΩ
Voltage range for level input:9V
~
30V
DI2- COM
Switch input
terminals 2
DI3- COM
Switch input
terminals 3
DI4- COM
Switch input
terminals 4
DI5- COM
Switch input
terminals 5
DI6- COM
Switch input
terminals 6
DI7/HI-COM
Switch input
terminals 7 OR
High-speed
pulse input
Besides features of DI1–DI6, it can be
used for high-speed pulse input.
Maximum input frequency: 100 kHz
Analog
output
AO1-GND
Analog output
terminal 1
Output voltage range:DC 0
~
10V/0
~
20mA
,
decided by toggle switches