FR500A&FR510A Series Vector Control Inverter
- 47 -
1: Terminal control (LED on)
2: Communication control (LED
blinking)
F02.01
Running direction
0: Forward
0
△
1: Reverse
F02.02
Reverse-proof action
0: Reverse enabled
0
×
1: Reverse disabled
F02.03
Dead time between
forward and reverse
0.0
~
6000.0s
0.0s
×
F02.04
Start mode
Unit’s place: Start Mode
0:Start directly
1:Rotational speed track and
restart
00000
×
Ten’s place: short-circuit detection
function
0:Ungrounded short-circuit
detection
1:Grounding short-circuit
detection before the first starts
2:Grounding short-circuit
detection before each starts
Hundred’s place: Speed tracking
0:Track from zero speed
1:Track from max frequency
Thousand’s place: Select if Jog
function takes the priority
0:Disable
1:Enable
Ten thousand’s place: Tracking
direction
0: Last direction when stop
1: Positive direction
2: Negative direction
3: Starting direction
F02.05
Start frequency
0.00
~
10.00Hz
0.00Hz
×
F02.06
Startup frequency
holding time
0.0
~
100.0s
0.0s
×
F02.07
Startup DC brakin
current
0.0
~
150.0%
0.0%
×
F02.08
DC braking time at start
0.0
~
100.0s
0.0s
×
F02.09
Speed search current
0.0
~
180.0%
130.0%
△
F02.10
Sped search decel time
0.0
~
10.0s
1.0s
×
F02.11
Sped search coefficient
0.01
~
5.00
0.30
△
F02.12
Stop mode
0: Ramp to stop
0
×
1: Coast to stop
F02.13
Initial frequency of stop
DC braking
0.01
~
50.00Hz
2.00Hz
×
F02.14
Stop DC braking current
0.0
~
150.0%
0.0%
×
F02.15
Waiting time of stop DC
braking
0.0
~
30.0s
0.0s
×
F02.16
Stop DC braking time
0.0
~
30.0s
0.0s
×
F02.17
Dynamic brake
0: Disabled
0
×
1: Enabled
2: Enabled at running
3: Enabled at deceleration
F02.18
Voltage of dynamic
480
~
800V
700V
×