6.6.5
Set up 1 – Relays
To enter the menu, proceed as follows:
⇒
⇒
CHOICE
(default = bold)
INFO
NAMUR:
Relay 1:
Relay 2:
Relay 3:
Relay 4:
Relay 5:
off
N/C
N/C
N/C
N/C
N/C
Contact functions
You can assign the function of up to 5 relays here. The relays 1 and 2 will be assig-
ned to an activated NAMUR function and will not be available for other functions
(compare with page 27).
Selection:
N/C / Controller / Limit / CCW / CCC
N/C
: no function
Controller
:
Controller control using relay
Limit
: Limit contactor function
CCW
: Chemoclean water. Water supply for the Chemoclean function.
CCC
: Chemoclean cleaner. Cleaner supply for the Chemoclean function.
(Together, CCC and CCW form the "Chemoclean" function. You can find
information on Chemoclean on page 98 ).
The limit value/controller contacts are configured in the menu "PARAM"
➠
"Set
up 2"
➠
"Controller settings".
!
Note!
•
Danger of data loss.
If you change the relay allocation
after
configuring the
controller and the number of relays available to the controller is
reduced
, the
complete
controller settings (see page 74) are reset to the default values.
• If you change the relay assignment for the controller, you must use the controller
menu (see page 74) to reassign all the functions selected there to a relay.
Example
: Relays 4 and 5 are assigned to the controller and you change the
controller assignment to relays 5 and 6 (number of relays remains 2)
(no data loss, providing the number of assigned relays is not reduced!).
• You can only activate the NAMUR, when the required relays 1 and 2 are free
Active open
Active closed
Selection acc. to NAMUR:
(only, if NAMUR is activated)
Assignment of NAMUR contacts as "Active open" contact (= normally closed
contact, opens when relay active) or "Active closed" contact (= normally open
contact, closes when relay active).
If the NAMUR function is enabled, the alarm, relay 1 and relay 2 contacts are given
the following functions:
• "Failure" = Fault signalling contact (terminals 41/42): Failure alarms are active if
the measuring system is not working correctly or if process parameters have
reached a critical value.
• "Maintenance required " = Relay 1 (terminals 47/48): Warning messages
become active when the measuring system is working correctly but requires
maintenance or a process parameter has reached a value which requires
intervention.
• "Function check" = Relay 2 (terminals 57/58): This contact is active during
calibration, maintenance, configuration and during the automatic cleaning cycle.
Active open
Active closed
Selection of controller contacts as "Active open" contact or "Active
closed" contact
(only, if controller is selected)
Active open
Active closed
Selection of limit values as "Active open" or "Active closed" contact
(only, if limit values are selected)
PARAM
pH
7.00
Param
Parametrieren
Grundeinstellung
Sonderfunktionen
Handbedienung
Quick
Setup
Edit
Weiter E
pH
7.00
Hold
Param
Settings
Set up 1
Set up 2
Manual operation
First start up
Edit
Next E
pH
7.00
Param
Set up 1
Sensor input
Display
Access codes
Current output
Relays
Edit
Next E
Hold
Hold
pH
7. 00
Param
[¯ ®]
[E]
Relay funct.
Next
Acc.Namur
off
Select
Relay 1
N/C
Relay 2
N/C
Relay 3
N/C
¯Relay 4
N/C
Содержание Topclean S CPC30
Страница 154: ...10 Technical data Topclean S 154 Endress Hauser...
Страница 156: ...11 Appendix Topclean S 156 Endress Hauser C07 CPC30xxx 19 06 08 en 006 eps...
Страница 157: ...Topclean S 11 Appendix Endress Hauser 157 C07 CPC30xxx 19 06 08 en 007 eps...
Страница 158: ...11 Appendix Topclean S 158 Endress Hauser C07 CPC30xxx 19 06 08 en 008 eps...
Страница 159: ...Topclean S 11 Appendix Endress Hauser 159...
Страница 160: ...11 Appendix Topclean S 160 Endress Hauser C07 CPC30xxx 19 06 08 en 002 eps...
Страница 161: ...Topclean S 11 Appendix Endress Hauser 161 C07 CPC30xxx 19 06 08 en 003 eps...
Страница 162: ...11 Appendix Topclean S 162 Endress Hauser C07 CPC30xxx 19 06 08 en 014 eps...
Страница 163: ...Topclean S 11 Appendix Endress Hauser 163 C07 CPC30xxx 19 06 08 en 015 eps...
Страница 164: ...11 Appendix Topclean S 164 Endress Hauser C07 CPC30xxx 19 06 08 en 011 eps...
Страница 165: ...Topclean S 11 Appendix Endress Hauser 165 C07 CPC300xx 19 06 08 en 010 eps...
Страница 166: ...11 Appendix Topclean S 166 Endress Hauser C07 CPC30xxx 19 06 08 en 012 eps...
Страница 167: ...Topclean S 11 Appendix Endress Hauser 167 C07 CPC30xxx 19 06 08 en 013 eps...
Страница 176: ...Index Topclean S 176 Endress Hauser...
Страница 178: ...www endress com worldwide BA236C 07 en 11 04 51504339 Printed in Germany FM SGML 6 0 DT...