6 Commissioning
Topclean S
82
Hauser
+Relay
–Relay
Motor run time
Xsd
n.c.
n.c.
060.0s
04.0%
Relay selection
(for three-point step controller)
+Relay
: Open the valve further (= increase dosing)
–Relay
: Close the valve further (= reduce dosing)
Selection: n.c. (= not connected). After this, the relays which have
been released in the Contacts menu are always offered as the
default.
!
Note!
If you cannot select a relay here, use the "Contacts" menu to make
relays available for the controller function.
Motor run time
: The time the motor drive requires to move the
valve from completely closed to completely open. The CPM153
requires this to be able to calculate the required pick-up time of
the relay for any required position change.
Xdg
: Maximum differential gap between valve and position feed-
back. If the difference is greater than the edited value, it will be
compensated by position changes.
!
Note!
The CPM153 expects feedback from the actuator drive about the
current valve position via a current or resistance input.
Relay:
max. pulse frequency
n.c.
120/min.
Relay selection
(for pulse frequency)
Relay
:
Relay selection
max. pulse frequency
: Input of the maximum pulse frequency.
(Pulses with a higher frequency are not forwarded to the relay).
(Maximum setting: 120 min
-1
)
Relay:
Period:
t
E
min:
n.c.
000.0 s
000.0 s
Relay selection
(for pulse length)
Relay
:
Relay selection
Period
:
Period length T in seconds (Range 0.5 ... 999.9 s)
t
E
min
: Minimum switch-on period. (Shorter pulses are not
forwarded to the relay thus going easy on the actuators.)
Current output 2
0 ... 20 mA
4 ... 20 mA
Current output 2
(for current output)
Selection of the current range, which should be output at the
current output.
y=0%
0/4 mA
20 mA
Current output
Assign the current value which corresponds to 100 % dosing
medium provision.
Type:
With selection "two-sided":
Dosing via:
1 output
2 outputs
Control:
(This is only possible if you selected the continuous controller
under current output 2.)
1 output
: for control using the current output in the "split range"
method. Control logics are required which can control two
valves/pumps over one current input.
2 outputs
: If the valves are controlled with two relays.
CHOICE
(default = bold)
INFO
Hold
pH 7. 00
Param
[E]
Control signal
Next
Edit[¯]
1 output
2 outputs
Содержание Topclean S CPC30
Страница 154: ...10 Technical data Topclean S 154 Endress Hauser...
Страница 156: ...11 Appendix Topclean S 156 Endress Hauser C07 CPC30xxx 19 06 08 en 006 eps...
Страница 157: ...Topclean S 11 Appendix Endress Hauser 157 C07 CPC30xxx 19 06 08 en 007 eps...
Страница 158: ...11 Appendix Topclean S 158 Endress Hauser C07 CPC30xxx 19 06 08 en 008 eps...
Страница 159: ...Topclean S 11 Appendix Endress Hauser 159...
Страница 160: ...11 Appendix Topclean S 160 Endress Hauser C07 CPC30xxx 19 06 08 en 002 eps...
Страница 161: ...Topclean S 11 Appendix Endress Hauser 161 C07 CPC30xxx 19 06 08 en 003 eps...
Страница 162: ...11 Appendix Topclean S 162 Endress Hauser C07 CPC30xxx 19 06 08 en 014 eps...
Страница 163: ...Topclean S 11 Appendix Endress Hauser 163 C07 CPC30xxx 19 06 08 en 015 eps...
Страница 164: ...11 Appendix Topclean S 164 Endress Hauser C07 CPC30xxx 19 06 08 en 011 eps...
Страница 165: ...Topclean S 11 Appendix Endress Hauser 165 C07 CPC300xx 19 06 08 en 010 eps...
Страница 166: ...11 Appendix Topclean S 166 Endress Hauser C07 CPC30xxx 19 06 08 en 012 eps...
Страница 167: ...Topclean S 11 Appendix Endress Hauser 167 C07 CPC30xxx 19 06 08 en 013 eps...
Страница 176: ...Index Topclean S 176 Endress Hauser...
Страница 178: ...www endress com worldwide BA236C 07 en 11 04 51504339 Printed in Germany FM SGML 6 0 DT...