6 Commissioning
Topclean S
76
Hauser
2.
PFM
(PFM; "pulse-frequency controller")
Pulse-frequency-modulated outputs are intended to control magnetic dosing pumps, for example.
As with PWM, PFM is output as a rhythmic signal by the relay.
The greater the calculated actuating variable, the higher the frequency of the related contact. The
maximum settable frequency 1/T is 120 min
-1
. The switch-on period t
ON
is a constant factor of the
entered frequency (see fig. 39).
For 100 % dosing, the ratio of switch-on period and switch-off period is 50 : 50.
Here, you can combine PFM with a second controlling method for a two-sided process as follows:
• a PFM relays
• a PWM relay
• a three-point step controller
C07-CPM153xx-05-06-00-en-004.eps
ƒig. 39:
Left: pulse-width modulation (PWM)
Right: pulse-frequency modulation (PFM)
3.
Three-point step controller
("3-point step")
With the Mycom S, this type of control is only possible for
one
process side (acid
or
base). With two-
sided processes, either PWM or PFM must be used for the other process side.
The three-point step controller can only be selected if an analogue input for the position feedback
of the valve or the actuator is available.
This type of actuator controller is intended for actuator drives (e.g. motor-driven valves, etc.) where
a motor must be controlled directly. For this, two relays are required: one "+relay" which, by
picking-up, opens the valve and one "–relay" which closes the valve. To set an actuating variable of,
for example, 40% (valve 40% open), Mycom S requires the input of the time that the "+relay" must
be picked up to completely open a completely closed valve (= "
motor run time
").
!
Note!
• If using a driven valve, gate valve or similar, you must determine the motor run time,
before
beginning with the menu settings.
• When commissioning your system, you need to fully open and close the valve so that Mycom S
can adjust the position feedback.
4.
Analogue
(via current output 2, 20 mA)
The current output can be used to output the
analogue
actuating variable for one or two-sided
processes and
cannot
be combined with the method described above.
• With
one-sided
processes, the actuating variable range 0% ... 100% (or –100 % ... 0%) is
represented on the selected current range (0 ... 20 mA or 4 ... 20 mA). The output current is
proportional to the actuating variable.
• With a
two-sided
process, the complete actuating variable range from –100% ... +100% is
represented on the given current range. A actuating variable of 0% leads to a current of 10 mA
(at 0 ... 20 mA) or 12 mA (at 4 .. 20 mA) (see fig. 40).
T
1
( f <)
T
2
(f >)
on
on
off
off
t
ON
t
ON
t
OFF
period T
time [s]
time [s]
contact
contact
Содержание Topclean S CPC30
Страница 154: ...10 Technical data Topclean S 154 Endress Hauser...
Страница 156: ...11 Appendix Topclean S 156 Endress Hauser C07 CPC30xxx 19 06 08 en 006 eps...
Страница 157: ...Topclean S 11 Appendix Endress Hauser 157 C07 CPC30xxx 19 06 08 en 007 eps...
Страница 158: ...11 Appendix Topclean S 158 Endress Hauser C07 CPC30xxx 19 06 08 en 008 eps...
Страница 159: ...Topclean S 11 Appendix Endress Hauser 159...
Страница 160: ...11 Appendix Topclean S 160 Endress Hauser C07 CPC30xxx 19 06 08 en 002 eps...
Страница 161: ...Topclean S 11 Appendix Endress Hauser 161 C07 CPC30xxx 19 06 08 en 003 eps...
Страница 162: ...11 Appendix Topclean S 162 Endress Hauser C07 CPC30xxx 19 06 08 en 014 eps...
Страница 163: ...Topclean S 11 Appendix Endress Hauser 163 C07 CPC30xxx 19 06 08 en 015 eps...
Страница 164: ...11 Appendix Topclean S 164 Endress Hauser C07 CPC30xxx 19 06 08 en 011 eps...
Страница 165: ...Topclean S 11 Appendix Endress Hauser 165 C07 CPC300xx 19 06 08 en 010 eps...
Страница 166: ...11 Appendix Topclean S 166 Endress Hauser C07 CPC30xxx 19 06 08 en 012 eps...
Страница 167: ...Topclean S 11 Appendix Endress Hauser 167 C07 CPC30xxx 19 06 08 en 013 eps...
Страница 176: ...Index Topclean S 176 Endress Hauser...
Страница 178: ...www endress com worldwide BA236C 07 en 11 04 51504339 Printed in Germany FM SGML 6 0 DT...