System integration
Liquistation CSF39
42
Hauser
7.2
Service interface
You can connect the device to a computer via the service interface and configure it using
"FieldCare" . Furthermore, configurations can also be saved, transferred and documented.
7.2.1
Connection
1. Connect the service connector to the interface on the Liquiline base module and
connect it to the Commubox.
2. Connect the Commubox via the USB connection to the computer on which FieldCare
is installed.
FieldCare
Service
FXA291
A0039618
51
Connection overview
7.2.2
Establishing the data connection
1. Start FieldCare.
2. Establish a connection to the Commubox. To do so, select the "CDI Communication
FXA291" ComDTM.
3. Then select the "Liquiline CM44x" DTM and start configuration.
You can now start online configuration via the DTM.
Online configuration competes with onsite operation, i. e. each of the two options blocks
the other one. On both sides it is possible to take away access from the other side.
7.2.3
Operation
• In the DTM the menu structure corresponds to the onsite operation. The functions of the
Liquiline soft keys are found in the main window on the left.
• Clicking a menu name or a function corresponds to pressing the navigator.
• You can make your settings conveniently via the computer keyboard.
• You can use FieldCare to save logbooks, make backups of configurations and transfer
configurations to other devices.
• You can also print out configurations or save them as PDFs.
7.3
Fieldbuses
7.3.1
HART
You can communicate using the HART protocol via current output 1.
1. Connect the HART modem or HART handheld terminal to current output 1
(communication load 250
‐
500 Ohm).
2. Establish a connection via your HART device.