Menu/Setup/Sampling programs/Setup program/New/Basic
Function
Options
Info
Bottle synchronization
Selection
• None
• 1. bottle change time
• 1. Time of
bottle number
Factory setting
None
None
The sampling and bottle change times are
not synchronized.
1. bottle change time
Sampling starts with the first bottle. Set the
synchronization time.
1. Time of bottle number
Each bottle is assigned to a specific fill time.
Set the synchronization time and the
weekday.
Having selected
Bottle change mode
External signal
Bottle chg. sig. input
Selection
• No bottle change input
configured
•
Binary input
Sx
Factory setting
No bottle change input
configured
The bottle change input can be configured
under
Inputs
.
A binary input must be configured for this
function. The sampling input can be
configured under "Inputs".
Multiple bottles
0 ... 23
The configuration options
depend on the current
number of bottles
Factory setting
0
Multiple bottles
"Simultaneous" transfer of two samples to
separate bottles.
Start condition
Selection
• Immediate
• Date/time
Factory setting
Immediate
The sampling program can be started either
immediately or at a specific, configurable
time.
Having selected
Start condition
Immediate
Sample at start
Selection
• Yes
• No
Factory setting
Yes
Yes
The first sample is taken when the program
is started.
No
The system waits for the interval to elapse
before the first sample is taken.
Having selected
Start condition
Date/time
Start date
01.01.2000 ... 31.12.2099
Factory setting
DD.MM.YYYY
Set the start date for the sampling program.
The format depends on the option
configured under general settings.
Start time
00:00:00 ... 23:59:59
Factory setting
HH:MM:SS (24h)
Set the time when the sampling program is
started. The format depends on the option
configured under general settings.
Stop condition
Selection
• Program end
• Continuous
Factory setting
Program end
Program end
The device stops sampling automatically
once it has run through the set program.
Continuous
The device runs through the set program
continuously in an infinite loop. Do not
forget to empty the bottles.