Operation
Liquistation CSF39
104
Hauser
Menu/Setup/Outputs/Alarm relay or relay at channel no.
Function
Options
Info
Function
Selection
• Off
• Limit switch
• Controller
• Diagnostics
• Cleaning
(sensor)
• Formula
(sensor)
Factory setting
• Alarm relays:
Diagnostics
• Other relays:
Off
The following functions depend on the option
selected.
These versions are illustrated individually in the
following sections to provide a clearer
understanding of the options.
Function
=
Off
Switches off the relay function and means no
further settings are required.
Outputting the status of a limit switch
Function = Limit switch
Function
Options
Info
Source of data
Selection
Limit switch 1 ... 8
Factory setting
None
Select the limit switch via which the status of the
relay is to be output.
The limit switches are configured in the menu:
Setup
/
Additional functions
/
Limit switches
.
Use the
ALL
and
NONE
soft keys to select
or deselect all the limit switches in one go.
Hold behavior
Selection
• Freeze last value
• Fixed value
• Ignore
Factory setting
Ignore
Outputting diagnostics messages via the relay
If a relay is defined as a diagnostic relay (
Function
=
Diagnostics
), it works in the
"fail-
safe mode"
.
This means that the relay is always energized ("normally closed", n.c.) in the basic state if
an error is not present. In this way it can also indicate a drop in voltage, for example.
The alarm relay always works in the failsafe mode.
You can output two categories of diagnostic messages via the relay:
• Diagnostic messages from one of the 4 Namur classes
• Diagnostic messages which you have individually assigned to the relay output
A message is individually assigned to the relay output at 2 specific points in the menu:
•
Menu
/
Setup
/
General settings
/
Extended setup
/
Diagnostics settings
/
Diag. behavior
(device-specific messages)
•
Menu
/
Setup
/
Inputs
/<Sensor>/
Extended setup
/
Diagnostics settings
/
Diag. behavior
(sensor-specific messages)
Before being able to assign the relay output to a special message in
Diag. behavior
you must first configure
Outputs
/Relay x:y or /
Alarm relay
/
Function
=
Diagnostics
.