Operation
Liquistation CSF39
110
Hauser
Menu/Setup/Additional functions/Limit switches/Limit switch 1 ... 8
Function
Options
Info
Range lower value
Settings depend on the
measured value
Operating mode
=
Out of range check
or
In
range check
Range upper value
1
2
t
MV
t
1
t
2
t
3
t
4
A
B
3
3
1
2
t
MV
t
1
t
2
t
3
t
4
3
A0028524
56
Range monitoring outside (A) and within (B) a range (without hysteresis and switch-on delay)
1
End of range
2
Start of range
3
Alarm range
t
1-4
An event is generated
• If measured values (MV) are increasing, the relay contact is closed when the switch-on point is exceeded
(
Range lower value
+
Hysteresis
) and the start delay (
Start delay
) has elapsed.
• If measured values are decreasing, the relay contact is reset when the switch-off point is undershot (
Range
upper value
-
Hysteresis
) and after the drop-out delay (
Switch off delay
).
Hysteresis
Settings depend on the
measured value
Operating mode
≠
Change rate
1
3
t
MV
t
1
t
2
2
A0028525
57
Hysteresis taking the example of limit value
overshoot
1
Limit value
2
Alarm range
3
Hysteresis range
t
1,2
An event is generated
The hysteresis is needed to ensure a stable
switching behavior.
The device software adds or subtracts the value
set here to/from the limit value (
Limit value
,
Range lower value
or
Range upper value
). This
results in double the
Hysteresis
value for the
hysteresis range around the limit value. An
event is then only generated if the measured
value (MV) completely passes through the
hysteresis range.
Start delay
Operating mode
≠
Change
rate
0 to 9999 s
Factory setting
0 s
Synonyms: pick-up and drop-out delay
Switch off delay
Operating mode
≠
Change
rate