Operation
Proline Promass 83
44
Hauser
18
Write TAG, descriptor and date
Access = write
With this parameter, you can store an 8 character
TAG, a 16 character descriptor and a date:
– Bytes 0-5: TAG)
– Bytes 6-17: Descriptor
– Byte 18-20: Date
Displays the current information in the device:
– Bytes 0-5: TAG
– Bytes 6-17: Descriptor
– Byte 18-20: Date
20
(HART 7)
Read long HART tag name
Access type = read
none
The long tag name with the international character
set (ISO Latin 1) makes it possible to use longer
names as required by many users in industry.
The long tag name occupies 16 consecutive buffer
memory addresses.
32 characters are saved in ASCII format, the first
character in the least significant byte (LSB) of the
lowest buffer memory address.
21
(HART 7)
Read unique ID assigned to long
HART tag name
Access type = read
none
This command can either be issued with the long
frame address of the device or the broadcast
address
No response if the long HART tag name and the
device do not match.
This comparison is case-sensitive.
If the long frame address is used, no response if the
address and the long HART tag name of the device
do not match
22
(HART 7)
Write long HART tag name
Access type = write
Byte 0-31: Long HART tag name response codes
Response codes
Code
Class
Description
0
Success
No command-specific errors
1-4
Undefined
5
Error
Too few data bytes received
6
Error
Device-specific command error
7
Error
In write protect mode
8-15
Undefined
16
Error
Access Restricted
17-31
Undefined
32
Error
Busy (A DR cannot be started)
33
Error
DR Initiated
34
Error
DR Running
35
Error
DR Dead
36
Error
DR Conflict
Command No.
HART command / Access type
Command data
(numeric data in decimal form)
Response data
(numeric data in decimal form)