Operation
Proline Promass 83
54
Hauser
17-0
802
Advanced Diagnostics:
The reference density is outside the limit value, set in the corresponding
diagnosis function.
17-1
803
Advanced Diagnostics:
The temperature is outside the limit value, set in the corresponding diagnosis
function.
17-2
804
Advanced Diagnostics:
The tube damping is outside the limit value, set in the corresponding
diagnosis function.
17-3
805
Advanced Diagnostics:
The electrodynamic sensor is outside the limit value, set in the corresponding
diagnosis function.
17-4
731
The zero point adjustment is not possible or has been canceled.
17-5
471
The maximum permitted batching time was exceeded.
17-6
472
Under batching: The minimum quantity was not reached.
Over batching: The maximum permitted batching quantity was exceeded.
17-7
473
The predefined batch quantity point was exceeded.End of filling process
approaching
18-0
571
Batching is started and active (valves are open)
18-1
572
Batching has been interrupted (valves are closed)
18-2
339
Flow buffer:
The temporarily buffered flow portions (measuring mode for pulsating flow)
could not be cleared or output within 60 seconds.
18-3
340
18-4
341
18-5
342
18-6
343
Frequency buffer:
The temporarily buffered flow portions (measuring mode for pulsating flow)
could not be cleared or output within 60 seconds.
18-7
344
19-0
345
19-1
346
19-2
347
Pulse buffer:
The temporarily buffered flow portions (measuring mode for pulsating flow)
could not be cleared or output within 60 seconds.
19-3
348
19-4
349
19-5
350
19-6
121
I/O board and the amplifier board (software versions) are not compatible.
19-7
061
F-Chip is faulty or not plugged into the I/O board.
20-0
363
Current input:
The actual value for the current lies outside the set limits.
20-4
698
The measuring device is being checked on site via the test and simulation
device.
20-5
474
Maximum flow value entered is overshot.
20-6
806
Advanced Diagnostics:
The fluctuation of the operating frequency is outside the limit value set in the
corresponding diagnosis functions.
20-7
807
Advanced Diagnostics:
The fluctuation of the pipe damping is outside the limit value set in the
corresponding diagnosis functions.
Byte-bit
Error No.
Short error description
→