Proline Promass 83
Troubleshooting
Hauser
89
061
S: HW F-CHIP
$
: # 061
F
F-Chip transmitter:
1. F-Chip is defective.
2. F-Chip is not plugged into the I/O
board or is missing.
1. Replace the F-Chip.
2. Plug the F-Chip into the I/O board.
No. # 1xx
→
So
t
ware error
121
S: A / C COMPATIB.
!: # 121
F
Due to different software versions, I/O
board and amplifier board are only
partially compatible (possibly restricted
functionality).
!
Note!
– This message is only listed in the
error history.
– Nothing is displayed on the display.
Module with lower software version has either to be
actualized by FieldCare with the required software
version or the module has to be replaced.
No. # 2xx
→
Error in DAT / no communication
205
S: LOAD T-DAT
!: # 205
M
Transmitter DAT:
Data backup (downloading) to T-DAT
failed, or error when accessing
(uploading) the calibration values
stored in the T-DAT.
1. Check whether the T-DAT is correctly plugged
into the amplifier board
2. Replace the T-DAT if it is defective. Spare parts
Before replacing the DAT, check that the new,
replacement DAT is compatible with the
measuring electronics. Check the:
– Spare part set number
– Hardware revision code
3. Replace measuring electronics boards if necessary.
206
S: SAVE T-DAT
!: # 206
M
251
S: COMMUNICATION I/O
$
: # 251
F
Internal communication fault on the
amplifier board.
Remove the amplifier board.
261
S: COMMUNICATION I/O
$
: # 261
F
No data reception between amplifier
and I/O board or faulty internal data
transfer.
Check the BUS contacts
No. # 3xx
→
System limits exceeded
339
to
342
S: STACK CUR OUT n
$
: # 339 to 342
S
The temporarily buffered flow portions
(measuring mode for pulsating flow)
could not be cleared or output within 60
seconds.
1. Change the upper or lower limit setting, as
applicable
2. Increase or reduce flow, as applicable
Recommendations in the event of fault category =
FAULT MESSAGE (
$
):
– Configure the fault response of the output to
ACTUAL VALUE, so that the temporary buffer can
be cleared.
– Clear the temporary buffer by the measures
described under Item 1.
343
to
346
S: STACK FREQ. OUT n
$
: # 343 to 346
S
347
to
350
S: STACK PULSE OUT n
!: # 347 to 350
S
The temporarily buffered flow portions
(measuring mode for pulsating flow)
could not be cleared or output within 60
seconds.
1. Increase the setting for pulse weighting
2. Increase the max. pulse frequency, if the totalizer
can handle a higher number of pulses.
3. Increase or reduce flow, as applicable.
Recommendations in the event of fault category =
FAULT MESSAGE (
$
):
– Configure the fault response of the output to
ACTUAL VALUE", so that the temporary buffer can
be cleared.
– Clear the temporary buffer by the measures
described under Item 1.