REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
1
Open the compressor insulation.
2
Turn ON the power using the respective circuit breaker.
3
Start the unit operation via the central controller.
4
Listen to the compressor when it tries to operate. Judge if a mechanical lock is
present.
INFORMATION
If a mechanical lock is present, also check for the root cause of impurities in the
refrigerant causing mechanical lock of the compressor. See
A mechanical lock is present on the
compressor?
Action
Yes
Replace the compressor, see
227].
No
Perform an mechanical check of the
compressor, see
To perform a mechanical check of the compressor
Prerequisite:
First perform an auditive check of the compressor, see
221].
Prerequisite:
Stop the unit operation via the central controller.
1
Turn OFF the respective circuit breaker.
INFORMATION
For outdoor units ≥14 HP, the transportation stay for the compressor should be
removed. Otherwise vibration is not absorbed, which can lead to pipe crack. See
227].
2
Check the compressor dampers and piping for any damage.
a
a
1