Service manual
264
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
INFORMATION
Bridge connector X4A is not supplied with the spare part PCB. Transfer the bridge
connector X4A
5
Loosen and remove the 4 screws that fix the fan inverter PCB assembly.
6
Loosen and remove the 2 screws that fix the fan inverter PCB to the heat sink
plate.
7
Carefully pull the PCB at the side and unlatch the PCB supports one by one
using a small pair of pliers.
8
To install the new fan inverter PCB, see
To install the fan inverter PCB
1
Clean the heat sink surface and apply a thin layer of heat sink compound to
the heat sink surface.
2
Install the fan inverter PCB on its correct location.
3
Latch the PCB supports using a small pair of pliers to fix the PCB.
4
Install and tighten the 2 screws to fix the fan inverter PCB to the heat sink
plate.
5
Install and tighten the 4 screws to fix the fan inverter PCB assembly.
a
b
b
a
d
c
a
a
a
Connector
b
Screw
c
Connector X1A
d
Connector X4A
6
Connect all connectors to the fan inverter PCB.
7
Reinstall connector X4A which you recuperated from the removed PCB.