3
|
Components
Service manual
248
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
a
b
c
a
Tie strap
b
Expansion valve cover
c
Expansion valve motor
3
Pull the expansion valve motor to remove it from the expansion valve body.
INFORMATION
It may be needed to turn the expansion valve coil 1/8 turn counter clockwise to
unlock it. Make sure to note the correct orientation (position) of the expansion valve
coil before removal.
4
Cut all tie straps that fix the expansion valve motor harness.
5
Disconnect the expansion valve motor connector from the appropriate PCB.
See
"To perform an electrical check of the expansion valve"
245] for an
overview oft he expansion valve connectors and their locations.
6
To install the expansion valve motor, see
247].
To remove the expansion valve body
Prerequisite:
Recuperate the refrigerant from the refrigerant circuit, see
368].
Prerequisite:
If needed, remove any parts or insulation to create more space for
the removal.
1
Remove the expansion valve motor, see
247].
2
Cut the expansion valve pipes using a pipe cutter.
a
c
b
a
Expansion valve body
b
Expansion valve pipe
c
Pipe cutter
INFORMATION
The expansion valve and motor can have a different configuration / layout.
3
Remove the expansion valve body.