Troubleshooting
Service manual
53
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
INFORMATION
When the power is switched ON, the outdoor unit main PCB checks all expansion
valve coil windings by current check.
1
Perform a check of the main PCB. See
290].
Possible cause:
Faulty main PCB.
2
Perform a check of the lower heat exchanger expansion valve. See
244].
Possible cause:
Faulty lower heat exchanger expansion valve.
3
Perform
a
check
of
all
refrigerant
side
thermistors.
See
348].
Possible cause:
Faulty refrigerant side thermistor(s).
4
Perform a check of the refrigerant low pressure sensor. See
Possible cause:
Faulty refrigerant low pressure sensor.
5
Check if the refrigerant circuit is correctly charged. See
Possible cause:
Refrigerant overcharge.
6
Check if the power supply is conform with the regulations. See
Possible cause:
▪
Faulty or disturbance of the power supply (imbalance >10%),
▪
Power drop,
▪
Short circuit.
7
Perform a power reset. If the error disappears and is raised again after a
while, check for the presence of an external source causing electrical noise.
See
Possible cause:
External source may cause interference.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.32 E9-48-49-50 – Electronic expansion valve overcurrent error
Main error code
Sub error code
Unit
E9
48
Main
49
Sub 1
50
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.