6
|
Technical data
Service manual
467
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
Mode
1
st
code
Description function
2
nd
code
Description selection
11(21)
3
Fan setting of heating
01
Standard
02
Slight increase
03
Increase
6
Sensitivity presence sensor
01
High sensitive
02
Low sensitive
03
Standard
04
Disable presence sensor
7
Airflow adjustment
01
Manual setting (see mode 23-6
below)
02
ESP auto judgment completed
03
Start ESP auto judgment (if
control set to fan only + ON)
8
Compensation by floor sensor
01
Floor sensor disabled
02
Air suction temperature priority
03
Standard
04
Floor temperature priority
9
Compensation of floor
temperature
01
-4°C
02
-2°C
03
No correction
04
+2°C