Troubleshooting
Service manual
40
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
Overcurrent detected on
outdoor unit fan motor
M1F.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the fan inverter PCB A4P. See
259].
Possible cause:
Faulty fan inverter PCB A4P.
2
Perform a check of the outdoor unit fan motor M1F. See
Possible cause:
Faulty outdoor unit fan motor M1F.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.20 E7-06-18-30 – Outdoor unit fan motor M2F overcurrent error
Main error code
Sub error code
Unit
E7
06
Main
18
Sub 1
30
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
Overcurrent detected on
outdoor unit fan motor
M2F.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.