2
|
Troubleshooting
Service manual
26
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
Trigger
Effect
Reset
High pressure switch
opens due to high
pressure >safety value,
Unit will stop operating.
If field setting 2-15=1
(default): When pressure
drops below the reset
value, via the indoor unit
remote controller, cycle
OFF & ON.
If field setting 2-15=0:
When pressure drops
below the reset value,
press BS3 on main PCB on
outdoor unit, and then via
indoor unit remote
controller, cycle OFF &
ON.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check that all stop valves of the refrigerant circuit are open. See
363].
Possible cause:
Closed stop valve in the refrigerant circuit.
2
Check the required space around the outdoor unit heat exchanger. See
Possible cause:
Insufficient air flow or air by‑pass due to required space
specifications not met.
3
Clean the outdoor heat exchanger. See
Possible cause:
Dirty outdoor heat exchanger.
4
Perform a check of the high pressure switch. See
Possible cause:
Faulty high pressure switch.
5
Check if the refrigerant circuit is correctly charged. See
363].
Possible cause:
Refrigerant overcharge.
6
Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See
Possible cause:
Non‑condensables and/or humidity in the refrigerant circuit.
7
Check if the refrigerant circuit is clogged. See
363].
Possible cause:
Clogged refrigerant circuit.
8
Perform a check of the condenser side expansion valve. See
244].
Possible cause:
Faulty condenser side expansion valve.
9
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.