Troubleshooting
Service manual
124
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
Inverter PCB A6P detects
overcurrent or no rotation
at start-up.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check if the power supply is conform with the regulations. See
356].
Possible cause:
▪
Faulty or disturbance of the power supply (imbalance >10%),
▪
Power drop,
▪
Short circuit.
2
Check if the refrigerant circuit is clogged. See
363].
Possible cause:
Clogged refrigerant circuit.
3
Perform a check of the inverter PCB A6P. See
274].
Possible cause:
Faulty inverter PCB A6P.
4
Perform a check of the compressor M2C. See
Possible cause:
Faulty compressor M2C.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.110 L9-13-14-15 – Inverter PCB A3P output phase abnormality
Main error code
Sub error code
Unit
L9
13
Main
14
Sub 1
15
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.