3
|
Components
Service manual
312
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
One or both propeller fan blade
assemblies are damaged?
Action
No
Perform a mechanical check of the DC
fan motor assembly, see
To perform a mechanical check of the DC fan motor assembly
Prerequisite:
First perform a mechanical check of the propeller fan blade
1
Manually rotate the fan motor shaft. Check that it rotates smoothly.
2
Check the friction of the DC fan motor shaft bearing.
Is the DC fan motor shaft friction
normal?
Action
Yes
Perform an electrical check of the DC
fan motor assembly, see
No
Replace the DC fan motor assembly, see
313].
To perform an electrical check of the DC fan motor assembly
1
First perform a mechanical check of both DC fan motor assemblies, see
311].
2
Turn ON the power of the unit.
3
Activate
Cooling
or
Heating
operation via the Cool/Heat master user
interface.
4
Check the functioning of the outdoor unit fan.
Outdoor unit fan …
Action
Rotates continuously (without
interruption)
DC fan motor assembly is OK. Return to
the troubleshooting of the specific error
and continue with the next procedure.
Does not rotate or rotates for a short
time
Continue with the next step.
5
Stop the unit via the central controller.
6
Turn OFF the respective circuit breaker.
DANGER: RISK OF ELECTROCUTION
Confirm the rectifier voltage is below 10 V DC before proceeding, see
7
Check that the DC fan motor connectors (X1A on A4P for M1F and X1A on A7P
for M2F) are properly connected to the PCB.
8
Unplug the DC fan motor connectors X1A of both fans and measure the
resistance between the pins 1–2, 1–3, and 2–3 of the DC fan motor
connectors.
Result:
All measurements MUST be 4.44°Ω±5% at 20°C.