If non-return valve d is blocked:
▪
Liquid pressure and also discharge pressure will increase.
▪
Suction pressure will drop
▪
R3T and R7T temperatures will be drastically higher compared to R5T and R5T.
Is the non-return valve d blocked?
Action
Yes
Replace the non-return valve d, see
242].
No
Component is OK. Return to the
troubleshooting of the specific error
and continue with the next step.
3.6.2 Repair procedures
To remove the E-bridge assembly
Prerequisite:
Stop the unit operation via the central controller.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
315].
Prerequisite:
Close the stop valves of the refrigerant circuit.
Prerequisite:
Recuperate the refrigerant from the refrigerant circuit, see
368].
1
With a pipe cutter, cut 4 refrigerant pipes as indicated.
a
b
g
e
c
d
f
a
Expansion valve
b
Cut here