2
|
Troubleshooting
Service manual
115
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
7
Check if there is discharge air by-pass on installation location.
Possible cause:
External noise. Check further on how to eliminate external
factors.
8
Perform a check of the inverter PCB A3P. See
Possible cause:
Faulty inverter PCB A3P.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.101 L4-06-18-20 – Fan inverter PCB A4P high fin temperature
Main error code
Sub error code
Unit
L4
06
Main
18
Sub 1
20
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
Thermistor located inside
the power module of the
fan inverter PCB detects a
temperature higher than
a certain value.
Unit will stop operating.
Manual reset via remote
controller.
Outdoor unit power reset.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
Prerequisite:
Stop the unit operation via the central controller.
1
Turn OFF the respective circuit breaker.
DANGER: RISK OF ELECTROCUTION
Confirm the rectifier voltage is below 10 V DC before proceeding, see
356].
2
Check that the thermal interface grease is applied properly on the (PCB or
refrigerant piping) contact surface of the heat sink. Adjust if needed.
Possible cause:
Thermal interface grease NOT applied properly on the heat
sink.
3
Check if heat sink plate is correctly fixed with screws.
Possible cause:
Heat sink plate not correctly installed.