3
|
Components
Service manual
231
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
INFORMATION
The compressor dampers may look different.
7
Remove the bushings and keep them for re-use.
8
To install the compressor, see
To install the compressor
1
Check the state of the dampers. Replace if worn.
2
Install the 3 dampers in the correct location on the unit.
a
a
b
c
c
c
a
a
Nut
b
Compressor
c
Damper
INFORMATION
The compressor dampers may look different.
3
Remove the caps from the compression pipe and suction pipe.
CAUTION
The oil in the compressor is hygroscopic. Therefore remove the caps from the
compressor pipes as late as possible.
4
Supply nitrogen to the refrigerant circuit. The nitrogen pressure MUST NOT
exceed 0.02 MPa.
5
Wrap a wet rag around the compressor pipes and solder the compressor pipes
to the refrigerant pipes.