Troubleshooting
Service manual
196
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
Main
code
Sub code
Description
Main Sub 1 Sub 2
UA
00
Combination Abnormality
03
Combination Abnormality - Mix of R22, R407C, R410A Type Units Detected
16
Combination Abnormality - More Than 64 Indoor Units Detected On Same System
17
Combination Abnormality - Local Setting Abnormality
18
Combination Abnormality - Outdoor Unit Not Compatible With Indoor Units
(Refrigerant Type)
19
Combination Abnormality - Local Set Alarm
20
Combination Abnormality - Non Compatible Outdoor Unit in Multi Combination
21
Combination Abnormality - BPMK Unit(s) Detected
22
Branch Selector Box Abnormality – Single installation
23
Branch Selector Box Abnormality –Connected Indoor Unit Index too High
25
Branch Selector Box Abnormality –Transmission wire Abnormality between Branch
Selector Box and Outdoor Unit
26
Branch Selector Box Abnormality - Transmission wire Abnormality between Branch
Selector Box and Connected Indoor Units
27
Branch Selector Box Abnormality – No Branch Selector Box Detected
28
Branch Selector Box Abnormality –Non-compatible Branch Selector Box Detected
29
Branch Selector Box Abnormality – Connected Indoor Unit Index too Low
30
Combination Abnormality – Heat Pump and Heat Recovery Outdoor Units Detected
in Same Combination
31
Combination Abnormality - REMQ-U Unit Detected Without a Multi Combination
35
Combination Abnormality - REMQ-U Unit Detected in Wrong Combination
38
Combination Abnormality - Altherma Hydro Unit(s) Detected
39
Combination Abnormality - Incorrect Combination
43
Combination Abnormality - Incorrect Combination
49
Combination Abnormality - Wrong unit Combination
50
Combination Abnormality - High Temperature Hydrobox Detected Connected to a
BS Unit
51
Combination Abnormality - Only Hydrobox Units Detected
53
Branch Selector Box Abnormality – Branch Selector Box Dip Switch Abnormality
UF
01
Wiring and Piping Mismatch - Auto Address Inconsistency on F1-F2 Transmission
05
Wiring and Piping Mismatch - Stop Valve(s) Closed or Incorrect
11
Wiring and Piping Mismatch - Excess Connection Ratio
UH
01
Auto Address Failure, Wiring Error
02
Auto Address Failure
E-1
-
Refrigerant Leak Check is not possible
E-2
-
Refrigerant Leak Check cannot be performed - Indoor Air Temperature is out of
range.