3
|
Components
Service manual
352
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
▪
E.g. R3T thermistor:
▪
Measured temperature with contact thermometer: 23.1°C,
▪
Resistance value determined through temperature (using the table for type
1 thermistors):
Resistance at 23°C: 21.85 kΩ,
Resistance at 24°C: 20.90 kΩ,
▪
Disconnect connector and measure resistance between X30A pin 1‑2:
Measured resistance: 21.8 kΩ,
▪
Measured resistance value is inside the range. R3T thermistor passes the
check.
INFORMATION
All thermistors have a resistance tolerance of 3%.
INFORMATION
Connect the service checker tool to the unit or use field settings mode 1 (see
455]) to monitor the thermistors.
If the measured resistance value matches the resistance determined through the
measured temperature, but the temperature for the corresponding thermistor via
service checker tool or field settings mode 1 is NOT correct, replace the applicable
PCB.
Does the measured resistance of the
thermistor match with the
temperature determined resistance?
Action
Yes
Thermistor is OK. Return to the
troubleshooting of the specific error
and continue with the next procedure.
No
Replace the specific thermistor, see
352].
Repair procedures
To remove the thermistor
Prerequisite:
Stop the unit operation via the central controller.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
315].
1
Locate the thermistor that needs to be removed.
2
Cut the tie strap that fixes the insulation and the thermistor wire.