Troubleshooting
Service manual
204
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
Symptom
Possible failure
Root cause
Repair
Disturbing operation noise
and vibration
Faulty Inverter PCB output Instable output voltage
from inverter PCB to
compressor(s)
Check Power Supply, see
356]. Restore the
power supply in conform
with the requirements.
Check inverter PCB(s) and
perform a power transistor
check, see
274]. Check
compressor(s), see
Installation faults
Unit not installed according
to installation manual
Check installation manual.
Correct necessary items.
Leave required space to
outdoor unit for operation
Wet operation
Liquid compression
Check thermistors. See
Check for refrigerant
overcharge, see
363]. Check
expansion valves for heat
exchanger that run as
evaporator. Check
superheat. Recover
refrigerant and weigh.
Charge refrigerant to the
correct amount
Flash gas on liquid piping
Expansion valve fault of
refrigerant shortage
Check expansion valves for
heat exchangers that run
as evaporator. Check
superheat. Recover
refrigerant and weigh.
Charge refrigerant to the
correct amount
2.4.21 Other symptoms
Mode: Cooling
Low pressure
High pressure
Running current
Dirty air filters
Lower than normal
Lower than normal
Lower than normal
Air by-pass between air
inlet/outlet @indoor unit
Lower than normal
Lower than normal
Lower than normal
Non condensables (i.e air)
in refrigerant
Higher than normal
Higher than normal
Higher than normal
Moisture in refrigerant
*1
Lower than normal
Lower than normal
Lower than normal
Impurities (dust, burr, …)
in refrigerant
*2
Lower than normal
Lower than normal
Lower than normal
Refrigerant shortage
Lower than normal
Lower than normal
Lower than normal
Insufficient compression
*3
Higher than normal
Lower than normal
Lower than normal