3
|
Components
Service manual
318
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
4
Loosen and remove the short screw (c) that fixes the grounding wire to the
heat sinks.
5
Loosen and remove the screw (d) that fixes the Thermistor R1T mounting
bracket.
6
Using a screwdriver, carefully separate both heat sinks from the inverter
PCB’s.
WARNING
Thermal grease is applied to the heat sinks. Use gloves when separating the heat
sinks from the inverter boards.
7
Loosen and remove the 6 screws (e) that fix the inverter mounting plate.
a
b
a
Inverter mounting plate
b
Liquid cooling piping
8
Carefully pull the inverter mounting plate (a) to the front and tilt it. Pay
attention to the liquid cooling piping (b).
9
Disconnect the necessary wiring to have access to noise filter PCB's, the
reactors and - on the rear side of the inverter mounting plate - the inverter
PCB's and fan inverter PCB's.
3.15.3 To remove the plate work on single fan units
Prerequisite:
Stop the unit operation via the central controller.
1
Turn OFF the respective circuit breaker.