2
|
Troubleshooting
Service manual
61
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
Trigger
Effect
Reset
Discharge superheat
<10˚C for 90 minutes
(SH
Discharge
=T
Discharge
−
T
condensation
).
Unit will stop.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform
a
check
of
the
suction
pipe
thermistor.
See
348].
Possible cause:
Faulty suction pipe thermistor or connector fault.
2
Perform
a
check
of
the
discharge
pipe
thermistor.
See
348].
Possible cause:
Faulty discharge pipe thermistor or connector fault.
3
Perform a check of the refrigerant high pressure sensor. See
Possible cause:
Faulty refrigerant high pressure sensor.
4
Check if the refrigerant circuit is correctly charged. See
Possible cause:
Refrigerant overcharge.
5
Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See
363].
Possible cause:
Non‑condensables and/or humidity in the refrigerant circuit.
6
Perform a check of the evaporator side expansion valve. See
Possible cause:
Faulty evaporator side expansion valve.
7
Check for objects near the indoor unit that may block the airflow. See
372].
Possible cause:
Airflow of the indoor unit is blocked.
8
Clean the air filters of the indoor unit(s). See service manual of the respective
indoor unit(s).
Possible cause:
Faulty or clogged air filter.
9
Adjust external static pressure setting for ducted type indoor units, if
necessary.
10
Perform a check of the indoor unit fan motor. See service manual of the
respective indoor unit(s).
Possible cause:
Faulty indoor unit fan motor.
11
Perform a check of the indoor air thermistor. See indoor unit manuals to
check thermistors on indoor units.
Possible cause:
Faulty indoor air thermistor.
12
Check all indoor units operation in heating mode. Check for room
temperatures below 20°C. Check if caution disappears once rooms heat‑up. If
NOT, continue checking the cause of the wet operation.